Duct test day on a multifamily job often raises the same questions. Which number does the inspector want? Why did a unit pass one test and miss another? Most of the mix-ups come down to leakage to outside vs. total duct leakage. The two metrics sound alike, but they measure different things.
We wrote this guide to give builders and engineers a clear answer before testing starts. You’ll learn what each metric measures and which value the IECC checks. We’ll also cover why Southeast attics and crawlspaces matter so much. Keep reading to plan smarter and pass sooner.
Total duct leakage counts every CFM that escapes the ducts at 25 pascals, no matter where the air ends up. Leakage to outside counts only the air lost beyond the thermal envelope. To get it, we run a blower door and a duct blaster at the same time.
For IECC duct leakage compliance on the prescriptive path, the code checks total leakage. The 2021 IECC caps it at 4.0 CFM25 per 100 square feet of conditioned floor area. At rough-in, before the air handler is installed, the limit is 3.0.
In the Southeast, many garden-style and townhome projects run ducts through vented attics and crawlspaces. Duct leakage and unconditioned space problems cost the most there. Each leak dumps cooled air into a hot attic and pulls humid air back into the system.
Early rough-in testing catches crushed flex, open boots, and panned returns while the fixes are still cheap.
The right partner makes multifamily duct testing simple. Look for BPI or similar credentials and calibrated duct blasters. Make sure the tester knows the IECC edition your AHJ enforces. Ask whether they explain leakage to outside vs. total duct leakage results in plain terms and tell you which number your permit needs.
Volume matters too. A good team schedules around your phasing and tests buildings as they’re released. They should send unit-by-unit reports that list conditioned floor area, test pressure, and CFM25. Ask about rough-in testing, since it catches failures before drywall goes up. Fast retests and clear repair notes keep trades moving. Finally, choose a team that focuses on new construction, so they know how to keep a schedule on track.
Air Tight Solutions is a leading provider of energy efficiency testing and compliance services for new construction. Our certified team tests duct systems across the Carolinas and Georgia, with deep knowledge of IECC codes from 2009 to 2021.
We work as an extension of your crew. You get next-day scheduling, clear reports, and practical advice that helps every building reach final on time. Schedule a consultation with us.
The prescriptive path requires total duct leakage. Leakage to outside mostly applies to performance modeling, ENERGY STAR, and certain local programs.
The limit is 4.0 CFM25 per 100 square feet of conditioned floor area. At rough-in without an air handler installed, the limit drops to 3.0.
Ducts in vented attics and crawlspaces lose conditioned air outdoors. Hot, humid air also gets pulled in, which raises energy use and moisture risk.
Test at rough-in, before drywall goes up. Early testing catches problems while repairs are still quick and cheap, then confirm the results at final.
Yes. Leaks into neighboring units or shared chases count toward total leakage but not leakage to outside, so a unit can fail the code limit.